Advanced Data Entry for Dealers
Central One makes the subscriber database available to dealers via the internet. Each dealer or dealer employee has a unique employee number and password for logging in to the system. Access to edit the subscriber database can be enabled or disabled for any employee number. This document explains the use of the signal information and special instructions screens.

The top half of the signals screen shows a scrolling list of the signals that have been defined for the account. Use the up and down arrow keys to move up and down the list. Up to 128 signals can be defined. The bottom half of the screen will show the properties of the signal that is highlighted in the top half. To edit the properties of the highlighted signal press the enter key, then use the up and down arrows to move from field to field. When you finish entering or editing a signal, press the escape key to return to the list at the top of the screen.
The order that signals appear on the screen is significant. When a signal is received the software searches the list from the top down until it finds a matching code and zone. If no match is found, the software searches the signal list found in the template account (if any). If no match is found in a template the software checks the default table for the format in which the signal was received. The Contact ID, SIA, ITI and Radionics Modem 3 formats have extensive defaults described in Central One bulletins. Other formats such as pulse formats have no defaults so the invalid signal procedure table in the dealer’s database record is consulted. If no default is found the signal is considered invalid and is logged.
To insert a signal into the list at a specific point highlight the signal that is to follow the new signal and press the insert key. To delete a signal from the list, highlight it and press the delete key. A confirmation prompt will follow.
Each signal has twenty nine properties. The following is a summary of each signal property. Many of the properties will be discussed in greater detail later in this section.
Special Instructions
Screen:

Access to the special instructions screen is not given to new dealers. Once a dealer has a complete understanding of the use of the special instructions screen and agrees to use the screen in a way that is consistent with Central One policy (bulletin 3000) remote editing rights are granted. Whenever a special instruction screen is modified by a dealer a flag is set so that the data entry department may review the instructions for compliance. Most monitoring instructions can be automated or have a specific place in the database. The use of textual special instructions should be avoided whenever possible. When special instructions must be used they should be phrased in a manner consistent with operator training practices.
There are four sets of special instruction fields. These fields are guaranteed to be presented to the operator together and in the same order that they appear on the data entry screen. The first field contains the text of the instruction. The next two fields allow you to enter a start and end date for the instruction. If the start date is omitted the instruction is effective immediately. If the end date is omitted the instruction is permanent. The “Cancel alarm?” field must be “Y” if the instruction is to automatically cancel alarms and “N” if it isn’t. The eight “Applicable area(s):” fields allow partitioned systems to have instructions that pertain only to specific partitions. The “Applicable alarm type(s):” field consists of a list of alarm type mnemonics, optionally followed by zone lists. For example, “PAN BUR 3,7-10” would make the instruction apply to all panic signals and burglary signals on zones 3, 7, 8, 9, and 10. If you leave the “Applicable alarm type(s):” field blank the instruction will apply to all signals.
Some proper uses for the special instructions screen include:
1. When the directions to premises field is not adequate. The directions field was never intended to contain long, free form directions. It was intended to identify the name of the sub-division or development where the premises is located or the name of the nearest major cross street. Long directions are not needed or even accepted by most modern law enforcement call centers. They know the streets of their jurisdiction. But when long directions are required, the special instructions fields (four fields of fifty characters each) provide adequate space.
2. When additional information is required to call the main or alternate numbers, such as menu options and extensions that need to be dialed.
3. “DND PD without callout approval.” This instruction assumes that you have put the callout step ahead of the police dispatch step in each of the signal definitions. In the absence of this instruction the central station operator will dispatch the police if no one from the callout list could be contacted. This instruction is usually limited to BUR alarm types so “BUR” should appear in the “Applicable Alarm Type(s):” field.
4. You may place an email address in the “Instruction:” field. This will cause any signals covered by the instruction to be instantly emailed. If the instruction required operator action a follow up email will be sent showing the full disposition when the event is completed.
5. Zone “Anding”. This feature allows you to prevent a dispatch from a single trip from a motion detector or other false alarm prone device. It is covered in detail later in this section.
6. Information not needed for central station operations. Most dealers have their own filing system and customer database and do not need to use special instructions in this way. However it is acceptable to enter information, such as “panel in master bedroom closet”, etc., in a special instruction field and put “N” for no in all eight of the “Applicable Area(s):” fields so that the instruction will not be displayed to an operator when handling an alarm.
You have an NFPA fire alarm account (designated by “NFPA” appearing in the permanent comments field of the database) that sends contact id. You want the default procedure to apply to fire alarms but you do not want a runner dispatched on trouble signals. Enter “log trouble signals” in the “Instruction:” field. Enter “Y” for yes in the “Cancel alarms?” field. Enter “TBL” in the “Applicable alarm type(s):” field. Make sure all of the area fields contain “Y” for yes and the start and end date fields are all zeroes. When a trouble signal is received in Contact ID, SIA or Modem format the monitoring software will see that the account is NFPA and set up a runner response procedure. It will then cancel and log the trouble signal on the strength of this instruction. Using a special instruction in this circumstance relieves you from the need to define every possible trouble signal that the panel might send.
You have a swinger on zone seven and took corrective actions but you are not sure you were able to isolate the cause. The subscriber is facing false alarm fines and wants to avoid dispatching the police if this zone falses again. One option is to remove the police dispatch step on the signals screen. This would cause the operator to make verify calls and callout notifications but not dispatch the police if the zone trips. A disadvantage is that you must remember to restore the dispatch step when you are satisfied that the problem is corrected. If you (and the subscriber) wish to ignore the zone for a period of time to be sure it is fixed the best method is to use a special instruction. Enter “service watch” or some similar text in the “Instruction:” field. Put a reasonable end date in the “Through:” date field so that the zone will not be ignored after a reasonable period of days and you will not be required to remember to restore the zone to service. Enter “Y” for yes in the “Cancel Alarms?” field. Enter “BUR 7” in the “Applicable Alarm Types:” field. Note that you could use an alert message to accomplish the same thing.
High end alarm panels have zone anding features built in. The advantage of using the alarm panel’s feature is that the alarm will not sound until the conditions for an alarm have been satisfied. If your panel does not offer this feature or if you want the alarm to sound but you do not want a central station response until the conditions have been satisfied, zone anding can be accomplished using the special instructions fields of the Central One database.
An instruction may be entered into any of an account’s four special instruction fields. The syntax for the command is “AND: [zonelist] WITH: [zonelist]”. A zone list consists of a list of zone numbers, separated by commas, a range of zone numbers, separated by a dash, or a combination of both. For example, “1, 3, 7-12, 14, 16-22, 29” would be acceptable. It is not possible to include zone zero in a list.
Here is how zone anding works:
Here are some examples where the instruction is “And: 1 With: 2”:
Note: The result would have been the same if the instruction read, “And: 2 With 1”. When the zone number is found in either field the other field provides the list of zones to search for in the alarm history.
Here is an example where the instruction is “And: 2,4,6,8 With: 2,4,6,8”:
BUR Zone 2 is received. Alarm history is checked to see if any of zones 2, 4, 6 or 8 were received in the last two minutes. If so the new signal is presented to the operator. If not, the signal is cancelled. Two consecutive trips of zone 2 will result in operator action because zone 2 appears in both fields.
When should zone anding be used?
Every zone that consists of motion detectors is a good and proper candidate for zone anding. The use of zone anding will prevent the dispatching of police in response to a single trip from a motion detector. It is important to configure panels so that multiple trips are reported to the central station, up to a reasonable swinger shut down limit of three or more trips per zone.
It has become common to use a single fire alarm control panel to protect a group of systems, sometimes in separate buildings with separate addresses. Separate addresses require separate accounts and Central One offers a special low rate for fire alarm accounts that are members of a networked system. For policy on networked systems please read bulletin 3001.
When creating a networked system it is advantageous to keep the zone numbers for each separate account in a contiguous range. Let’s say you are protecting three buildings, A, B, and C. The panel is going to be installed in building A and will be account number 9990001. Building A has devices on zones 1 through 3. Building B has devices on zones 4 through 6, Building C has devices on zones 7 through 9. The signals in account 9990001 (building A) would be set up as follows:
Account 9990001:
|
Code |
From Zone |
To Zone |
Alarm Type |
Zone Comments |
|
113 |
1 |
1 |
FIR |
Water flow |
|
110 |
2 |
2 |
FIR |
General Fire |
|
203 |
3 |
3 |
SUP |
Gate Valve Tamper |
|
65535 |
4 |
6 |
SPC |
@9990002 |
|
65535 |
7 |
9 |
SPC |
@9990003 |
Zones 1 through 3 are set up and procedured in account 9990001. Zones 4 through 6 are relayed to account 9990002. Zones 7 through 9 are relayed to account 9990003. Placing 65535 in the code field causes any alarm code to match. It is a wild card value. In order to relay signals from one account to another you must place the “@” symbol in the first character of the “Zone Comments” field, followed by the account number where the signal should go. You must define the relayed signals in the destination accounts, as in:
Account 9990002:
|
Code |
From Zone |
To Zone |
Alarm Type |
Zone Comments |
|
113 |
4 |
4 |
FIR |
Water Flow |
|
110 |
5 |
5 |
FIR |
General Fire |
|
203 |
6 |
6 |
SUP |
Gate Valve Tamper |
Account 9990003:
|
Code |
From Zone |
To Zone |
Alarm Type |
Zone Comments |
|
113 |
7 |
7 |
FIR |
Water Flow |
|
110 |
8 |
8 |
FIR |
General Fire |
|
203 |
9 |
9 |
SUP |
Gate Valve Tamper |