------------------------------------------------------------------------- Radionics Modem III Signals & Default Procedure Bulletin 1034 04/09/03 Copyright (C) 2003, Central One All Rights Reserved ------------------------------------------------------------------------- The Radionics Modem 3 format sends a two hex digit alarm code (from 00 to FF) with optional modifiers for the area and point or user (zone) number. Each event is mapped to an equivalent SIA event. If no procedure for a particular event is defined in the subscriber account or template then the SIA equivalent procedure (as shown in bulletin 1033) will be used to handle the alarm. Undefined events without an equivalent SIA mapping will be logged without operator action. Code Decimal Description SIA Equivalent ---- ------- ----------------------------------------- -------------- 01 1 start listen in LF 292 02 2 bad call to ram LD 290 03 3 access granted DG 85 04 4 duress ZZ 676 05 5 user alarm command 7 PA 391 06 6 user alarm command 9 PA 391 07 7 bypass UB 522 08 8 force point CF 58 09 9 status alarm YY 649 0A 10 status trouble YY 649 0B 11 fire alarm FA 131 0C 12 fire trouble FT 150 0D 13 missing fire UZ 546 0E 14 fire restoral FR 148 0F 15 fire restoral FR 148 10 16 alarm BA 27 11 17 trouble BT 46 12 18 restore BR 44 13 19 missing alarm UZ 546 14 20 missing trouble UY 545 15 21 point opening OP 380 16 22 point closing CZ 78 18 24 point bus trouble US 539 19 25 points tested UX 544 1A 26 restore (not documented by Radionics) UR 538 1B 27 reset RN 456 1F 31 sensor reset XI 607 20 32 relay set RC 445 21 33 relay reset RO 457 22 34 was forced armed CW 75 24 36 fire walk test start FI 139 25 37 fire walk test end FK 141 28 40 fail to open OI 373 29 41 fail to close CI 61 2A 42 watch mode (alarm = start, restore = end) 2C 44 extra close time CE 57 2D 45 cancel BC 29 2E 46 status opening YY 649 2F 47 opening OP 380 30 48 forced close CF 58 31 49 status closing YY 649 32 50 closing CL 64 33 51 test report (may include up to 14 flags that produce arbitrary event codes) RP 458 34 52 log threshold JL 246 35 53 log overflow JO 249 36 54 params changed YG 631 37 55 user code tamper JA 235 38 56 user code changed JV 256 39 57 schedule executed JR 252 3A 58 schedule changed JS 253 3B 59 date changed JD 238 3C 60 time changed JT 254 3D 61 level changed JZ 260 3E 62 program access ok RB 444 3F 63 program access bad RD 446 40 64 ram access ok RB 444 41 65 ram access bad RD 446 42 66 trouble UT 540 43 67 comm restoral YK 635 44 68 phone line fail LT 306 45 69 phone line restoral LR 304 46 70 SDI failure ET 124 47 71 SDI restoral ER 122 48 72 a.c. power failure YP 640 49 73 a.c. power restoral YQ 641 4A 74 battery missing YM 637 4B 75 battery low YT 644 4C 76 battery restore YR 642 4D 77 watchdog reset YW 647 4E 78 temperature alarm DA 79 4F 79 remote reset RN 456 50 80 checksum fail YF 630 51 81 memory fail YF 630 52 82 reboot RN 456 53 83 params bad YF 630 54 84 forcee close perimeter instant CF 58 55 85 forced close perimeter delay CF 58 56 86 status perimeter instant YY 649 57 87 status perimeter delay YY 649 58 88 perimeter instant armed (closing) CL 64 59 89 perimeter delay armed (closing) CL 64 5A 90 PT user code delete JX 258 5B 91 PT user code restoral JY 259 5C 92 swinger bypass BB 28 5D 93 rf battery low XT 618 5E 94 rf battery restore XR 616 5F 95 tamper restore TR 512 60 96 rf receiver trouble XQ 615 61 97 early to open OH 372 62 98 late to open OJ 374 63 99 closing early CK 63 64 100 closing late CJ 62 65 101 extra rf point XE 603 66 102 rf receiver restore XJ 608 67 103 rf interference XQ 615 68 104 forced close early CF 58 69 105 forced close late CF 58 6A 106 tamper alarm TA 495 6B 107 tamper trouble TT 514 6C 108 bad 9112 packet RT 462 6D 109 forced close perimeter instant CF 58 6E 110 add card 6F 111 forced close CF 58 70 112 cycle door 71 113 unlock door 72 114 door secure 73 115 access denied LD 290 74 116 door open too late (alarm and restore) DL 90 75 117 request to (alarm = enter, restore = exit) 79 121 status opening YY 649 7A 122 forced close late PT CF 58 7B 123 checksum fail YF 630 7C 124 a.c. power restoral AR 18 7E 126 log overflow JO 249 80 128 start listen in LF 292 82 130 paper in VI 555 83 131 printer trouble VT 566 85 133 printer restoral VR 564 87 135 start listen in LF 292 89 137 -12V trouble YP 640 8B 139 event not sent RT 462 8C 140 ram access ok RB 444 8D 141 relay set RC 445 8E 142 event not sent RT 462 8F 143 trouble UT 540 91 145 door (alarm = unsecure, restore = locked) DS 97 92 146 time set JT 254 93 147 point bus trouble US 539 96 150 was force armed CF 58 97 151 fail to execute JP 250 98 152 log overflow JO 249 9B 155 status report YY 649 9E 158 trouble UT 540 9F 159 battery low YT 644 A1 161 status rf battery low XT 618 A2 162 perimeter delay armed CL 64 A3 163 zone status YY 649 A5 165 trouble UT 540 A6 166 trouble UT 540 A7 167 low battery YT 644 A8 168 user code tamper JA 235 A9 169 phone trouble LT 306 AA 170 extra point XE 603 AC 172 +5V trouble YP 640 B0 176 ram access failed RD 446 B1 177 low battery YT 644 B2 178 ram bypass B3 179 error B5 181 alarm BA 27 B6 182 fire walk test start FX 154 BA 186 closing CL 64 BB 187 log overflow JO 249 BC 188 error BD 189 log overflow JO 249 BE 190 sensor reset XI 607 BF 191 phone restored LR 304 C0 192 tamper restoral TR 512 C1 193 service required YX 648 C4 196 duress ZZ 676 (not an official SIA code) C5 197 zone status YY 649 C7 199 trouble UT 540 C8 200 phone trouble LT 306 CA 202 phone trouble LT 306 CE 206 status close late YY 649 D0 208 listen in start LF 292 D1 209 forced close late PI CF 58 D2 210 status closing YY 649 D3 211 phone restore LR 304 DA 218 status perimeter delay YY 649 DB 219 alarm BA 27 DC 220 log overflow JO 249 DD 221 computer trouble DE 222 12V trouble YP 640 E1 225 status closed late YY 649 E3 227 listen in LF 292 E4 228 bad 9112 packet RT 462 E5 229 12V trouble YP 640 E6 230 tamper restoral TR 512 E7 231 phone restoral LR 304 E9 233 trouble UT 540 EB 235 alarm BA 27 Additional information, such as point or user number and area number may be included with any event. For the test signal (code 33 hex, 51 decimal) the following status codes are translated to arbitrary event codes as follows: LT 257 log threshold JL 246 LO 258 log overflow JO 249 PT 259 point bus trouble US 539 PA 260 program access ok RB 444 RT 261 rf receiver trouble XQ 615 BC 262 bad call to ram RA 443 UT 263 user code tamper JA 235 SF 264 SDI failure ET 124 CF 265 communications failure YC 627 AC 266 a.c. power failure AT 20 BM 267 battery missing YM 637 BL 268 battery low YT 644 PB 269 params bad checksum YF 630 EP 270 extra rf point XF 604 When the additional modifiers PT (point), ID (user id), or RT (rf point) are received the number that follows is placed in the zone field. If more than one of these modifiers is received then the last one in the message is placed in the zone field. Other modifiers such as SK (SKD), CI (code id), SI (SDI failure), PHNL (phone line failure), and RY (relay) do not modify the code or zone fields. You can see the text of the message in the alarm log. The modifier for area or partition is fully supported.